TD11 has a room temperature sensor with active KP10 measuring element.
Application
TD11..15 and TDF12..15 are used to measure the room temperature.
The temperature sensors are used in conjunction with all Kieback&Peter loop controllers and control systems that have a sensor connection for the active KP10 measuring element.
Technical Data
Measured quantity: Room temperature in homes or offices
Measuring tolerance: Typically ±0.2K.
Measuring range: -20 °C to +60 °C.
Plastic housing, RAL 9010 (pure white).
Measuring element: KP10 active measuring element; 2.73 V at 0 °C; TC = 10 mV/K