Foam Chamber NF-FC100 & NF-FCSS100
Supplied by
National Fire Fighting Manufacturing Company
Foam chamber is defined by NFPA-11 as Type II discharge outlets for delivering the foam to the surface of a flammable liquid. The foam chambers are widely used with the inline foam inductor, balance pressure foam proportioning system, bladder tank proportioner or foam tender.
Flow Rate (LPM)
AFFF 3% (as per UL) - 600 - 2400
AFFF 3% (as per FM) - 658 - 1855
AFFF 6% (as per FM) - 653 - 1839
Inlet Size - 100 NB
Outlet Size - 200 NB
Features:
- Heavy duty welded construction with choice of Carbon Steel or Stainless Steel material
- Frangible Glass Vapour Seal
- Controlled Air Flow proportional to liquid flow for optimum foam quality and rupture of vapour seal in narrow pressure tolerances for increased reliability
- Field replaceable orifice plate fitted with Foam Chamber
Specifications
- Manufacturer:
- National Fire Fighting Manufacturing Company
- Model:
- NF-FC100 & NF-FCSS100
- Country of origin:
- UAE