Conventional control panel is conventional fire control panels provide two/four zones of fire detection. All panels have been designed to offer high standards of performance, reliability and quantity and comply fully with BS5839, Part 4, 1988 and EN 54 parts 2 and 4.
Operating Voltage: 220VAC ± 15%, 50Hz
Standard: BS5839, Part 4, 1988 and EN 54 parts 2 and 4
Operating Temperature: -10°C to 40°C @95% relative humidity
Number of Zones: Four Zone
Zone Capacity: 15 detectors (AOL); 25 detectors (EOLR)
Standby Batteries: 5 AH, 24hours monitoring state
Output Voltage: 20VDC to 28VDC
Static Loading Current: 2.5 mA (when connected with 15 conventional detector)
Fire Alarming Resistance: 150Ω-1.5kΩ (normal 470Ω)
End of Line Resistor: 4.7kΩ or AEOL (Active End Of Line)
No. of Sounder Output: 2
Sounder Output Current: 1 Ampere (500mA per output)
Sounder Output Voltage: 20VDC to 28 VDC
Aux. Power Output: 20VDC to 28VDC
Both end of line resistors and active end of line can be used
Programmable sounder circuits outputs
Zone Isolate control
Fully monitored sounder circuits
Key control evacuate over-ride
Class change terminals for remote control
Up to 15 fire detectors and infinite manuals call points each zone
Manufacturer: | National Fire Fighting Manufacturing Company |
Model: | P-C204A |
Country of origin: | UAE |
Certification | CE, LPCB |
Material | Coated Metal |
Application | Indoor Use |
Dimension (mm) | 380mm x 95mm x 320mm |