Control panel is surface mounting panel with grey in color and voltage about 115V. It is designed and manufactured to the highest standards in a quality controlled environment and with UL & FM approvals, the Shield A-XT releasing panel offers outstanding value and performance for all small to medium fixed firefighting installations. With three detection zones as standard, extinguish-ant release can be configured to activate from any combination of detection zone inputs to allow ( among other combinations) any two from three type activation's such as would be required for detection in ceiling void, room and floor void applications.The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguish-ant release for added user safety.
Size: 368 x 310 x 90
Construction: 1.2mm mild sheet steel
Finish: Epoxy powder coated
Colour - lid & box: Red RAL 3002 (optional grey BS 00 A 05 semi-matt)
Mains supply: 230V AC or 115V AC
Mains supply fuse: 1.6 Amp (F1.6A L250V)
Power supply rating: 3 Amps total including battery charge 28V +/- 2V
Battery charge voltage: 27.6VDC nominal
Battery charge current: 0.7A maximum
Battery fuse: 20mm, 3.15A glass
| Manufacturer: | National Fire Fighting Manufacturing Company |
| Model: | S115G-EXT |
| Country of origin: | UAE |
| Certification | UL Listed, FM Approved |
| Lighting Technology | LED |
| Ingress Protection | IP30 |