Control panel is surface mounting panel with grey in color and voltage about 230V. It is designed and manufactured to the highest standards in a quality controlled environment and with UL & FM approvals, the Shield A-XT releasing panel offers outstanding value and performance for all small to medium fixed firefighting installations. With three detection zones as standard, extinguish-ant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activation's such as would be required for detection in ceiling void, room and floor void applications.The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguish-ant release for added user safety.
Size: 368 x 310 x 90
Construction: 1.2mm mild sheet steel
Finish: Epoxy powder coated
Colour - lid & box: Red RAL 3002 (optional grey BS 00 A 05 semi-matt)
Mains supply: 230V AC or 115V AC
Mains supply fuse: 1.6 Amp (F1.6A L250V)
Power supply rating: 3 Amps total including battery charge 28V +/- 2V
Battery charge voltage: 27.6VDC nominal
Battery charge current: 0.7A maximum
Battery fuse: 20mm, 3.15A glass
Manufacturer: | National Fire Fighting Manufacturing Company |
Model: | S230G-EXT |
Country of origin: | UAE |
Certification | UL Listed, FM Approved |
Lighting Technology | LED |
Ingress Protection | IP30 |